Electrical Description
The integrated base sounder is line powered and needs no external power supply. It operates at 17–28V DC and is polarity-sensitive.
Mechanical Construction
The Intelligent Twin Input/Output Unit is available in the new faceplate style enclosure. This can be mounted with the supplied backbox for surface mounting or flush mounted using a UK double gang, flush mounting back-box of minimum depth 30mm.
EMC Directive 2014/30/EU
The Intelligent Twin Input/Output Unit complies with the essential requirements of the EMC Directive 2014/30/EU, provided that it is used as described.
A copy of the Declaration of Conformity is available from Apollo on request.
Conformity of the Intelligent Twin Input/Output Unit with the EMC Directive, does not confer compliance with the directive on any apparatus or systems connected to them.
Construction products regulation 305/2011
The Intelligent Twin Input/Output Unit complies with the essential requirements of the Construction Products Regulation 305/2011/ EU.
A copy of the Declaration of Performance is available from Apollo on request.
Product Information
The Intelligent Twin Input/Output Unit provides the function of two Input/Output Units within one enclosure. The two units are electrically independent of each other. There is a DIL switch on each unit to set the address.
Both input/output units in the enclosure provide supervision of one or more normally open volt free contacts connected to a single pair of cables and a set of changeover relay output contacts.
Key Features
Improved design for ease of wiring meaning faster installation
Contains controllable isolator *
Address range 1 - 254 *
Nine pre-configured modes, including compatibility mode from XP95/Discovery to CoreProtocol systems
Failsafe mode (meets BS 7273-4 requirements)
Configurable input styles
Earth fault monitoring
* Note: CoreProtocol enabled systems feature only, please check with your system partner for availability.