XP95 Optical Detector

Reference: 55000-600APO
Brand:
Category:
In stock

The XP95 optical smoke detector uses an internal flashing infrared LED and a photo diode at an obtuse angle. In clean air conditions, the photo diode in the XP95 detector does not receive light from the LED and produces a corresponding analog signal.

The signal increases when smoke enters the chamber and the light is scattered in the photo diode. The optical smoke detector has an LED indicator that emits red light when the detector is in alarm.

Share

10-year guarantee

Performance
Nominal Analog Value 7
Analog Value (- Tolerance) 7
Analog Value 25 + 7 / -7
Analog Value of Alarm Level 55
Chevron Type Chamber

Electrical
Protocol voltage (Min) 5V
Protocol voltage (max.) 9 V
Protocol voltage 5 to 9V peak to peak
Inrush current 1mA
Maximum start-up time 4 seconds
Status indicator – Red Alarm
Status indicator – Fault off
Quiescent current 340μA
Sampling frequency once per second
Sampling frequency + L2 Positive loop in and out, dual terminal
Terminal functions L1 In -L1 in Loop in and out, dual terminal
Terminal functions + R + R Remote indicator positive connection
Terminal functions -R -R Remote indicator negative connection
Polarity L1 and L2 are insensitive to polarity
Not battery-powered

From Environment
Humidity (Min) 0% RH
Humidity (Max) 95% RH
Humidity Note without condensation or frost
Humidity from 0% to 95% (without condensation or frost)

Brand Information
The XP95 range of analog addressable fire detectors uses tried and trusted technology to offer the best performance, with unique features that benefit the installer and the end user. It is suitable for medium to large applications with simple installation requirements.

Because it operates using digital communication, XP95 has high immunity to corruption and is therefore often preferred in large systems where security is critical. XP95 products are frequently used in commercial, industrial, financial, government, IT / telecommunications and healthcare applications.

Brand characteristics

  • Alarm buzzer for quick alarm reports
  • Alarm address for quick alarm location
  • XPERT 7 card addressing
  • Electronics-free base
  • Easy installation
  • Elegant design

Electrical Description

The detector is designed to be connected to a two-wire loop circuit that carries data and a 17V to 28V DC supply. The detector is connected to the input and output power supply via terminals L1 and L2 on the mounting base. A remote LED indicator requiring no more than 4 mA at 5 V can be connected between the +R and -R terminals. An earth connection terminal is also provided.

When the device is powered, the ASICs regulate the flow of energy and control data processing. The optical ASIC is controlled by the communication ASIC and pulses the IR LED. The signal from the photodiode is processed by the optical ASIC and transferred to the communication ASIC, where it is stored. When smoke enters the chamber, the photodiode signal increases.

The information for the A/D converter is updated once a second or when the monitor or previous address is interrogated.

Whenever the device is interrogated, this data is sent to the control equipment. The EN54 threshold alarm levels are calibrated in the processing ASIC. If the device is not addressed within one second of its last polling and the analog value is greater than the EN54 alarm level, the alarm flag is initiated and the device address is added to the data stream every 32 polling cycles from its last polling for the duration of the alarm level condition, except when the alarming device is being interrogated. This can provide a location-identified alarm of any device in the loop in approximately two seconds.

The detector is calibrated to provide an analog value of 25 ± 7 counts in clean air. This value increases with smoke density. A count of 55 corresponds to the EN54 alarm sensitivity level.

Operation
The XP95 optical detector has an indicator LED that turns white in standby and red in alarm. Inside the housing is a printed circuit board which, on one side, contains the lightproof maze camera with integrated screen around the optical measuring system and on the other side the address capture, signal processing and communications electronics.

An infrared light-emitting diode inside the collimator is arranged at an obtuse angle to the photodiode. The photodiode has an integral daylight blocking filter.

The IR LED emits a burst of collimated light every second.

In clean air, the photodiode does not receive light directly from the IR LED due to the angular arrangement and the double mask. When smoke enters the chamber, it scatters photons from the emitting IR LED to the photodiode in an amount related to the characteristics and density of the smoke. The signal from the photodiode is processed by the optical ASIC and passed to the A/D converter in the communication ASIC ready for transmission when the device is interrogated.

Application
The choice of detector in the XP95 range will depend on the type of fire risk, the fire load and the type of environment in which the detector is located.

For general use, smoke detectors are recommended as they provide the highest level of protection. Smoke detectors in the XP95 range can be optical or multisensor.

The multisensor is basically an optical smoke detector and will therefore respond well to smoke from smoldering fires.

The detector also senses air temperature. This temperature sensitivity allows the multisensor to respond to fast-burning (flaming) fires.

Where the environment is smoky or dirty under normal conditions, a heat detector may be more appropriate. It should be recognized, however, that any heat detector will only respond when the fire is well established and generating high heat output.

Device addressing
Each XP95 device responds to interrogation and commands from the central station. It communicates status information, command bits, type, location and other information to the central station, allowing an alarm to be triggered even when the device itself is not being interrogated. Message error checking is also provided. The devices are compatible with Discovery® systems and control equipment to help maintain, extend and upgrade existing systems.

A unique, patented XPERT card provides simple, user-friendly and accurate identification of the detector’s location, whereby a coded card, inserted into the base, is read by any detector once connected. All the electronics are in the detector, except for the location information which is retained in the base. The address card simplifies and speeds up installation and commissioning. Resolution errors during maintenance and service are eliminated.

XP95 detectors provide an alarm feature that automatically places an alarm flag in the data stream and reports its address when the preset EN54 limits are exceeded. The devices provide great flexibility in system design.

Communication
Compatible with XP95, Discovery and CoreProtocol

Maintenance service
Detectors should be maintained in accordance with BS 5839-1 or other locally applicable code. Test equipment can be ordered to test smoke and heat detectors.

Detectors should not be cleaned in the field, except for the careful removal of external dirt with a damp cloth. For cleaning and recalibration, the detectors must be returned to Apollo.

EMC Directive 2014/30 / EU
The XP95 optical smoke detector complies with the essential requirements of EMC Directive 2014/30 / EU, provided it is used as described.
A copy of the Declaration of Conformity is available on request.
The compliance of the XP95 optical smoke detector with the EMC directive does not confer compliance with the directive on any apparatus or system connected to them.

Construction Products Regulation 305/2011
The XP95 optical smoke detector complies with the essential requirements of Construction Products Regulation 305/2011 / EU.
A copy of the Declaration of Performance is available from Apollo on request.

Environmental characteristics
The XP95 optical smoke detector is not affected by wind or atmospheric pressure and operates in a temperature range of -20°C to +60°C.

Sem características de produto para apresentar.

Datasheet
Product Guide

Manufacturer information

Manufacturing information includes the address and related information of the product manufacturer

No information to present at the moment.

Responsible EU person

EU-based economic operator who guarantees that the product complies with the required regulations.

No information to present at the moment.

Product safety images

Product safety images contain information about product packaging and can provide key safety information for a specific product.

No information to present at the moment.

Related Products

Soteria Dimension Optical Detector – Specialist

Soteria Optical Detector

Thermal Detector Soteria

Soteria Multi-Sensor Detector

Find out more about this product. Contact us for more information.

Por favor preencha o formulário abaixo para solicitar mais informações.

Please fill in the form below to request more information.