Electrical Description
All devices are powered directly from the loop, requiring no external power supply. They operate on 17-28 V DC and are polarity sensitive.
Operation
A nominal sound output of 100dB(A) is achieved with a current consumption of 5mA in the case of the siren and 8mA for the audible indicator.
Many control panels will be capable of triggering up to 20 sirens and up to 15 sirens per loop, on average. The maximum number of devices that can be connected to a specific loop must, however, be determined by a loop loading calculation using the Apollo Loop Calculator. This is available on the Apollo website www.apollo-fire.co.uk.
Since alarm devices are intended for use in open areas, it is possible for more than one device to be audible at any point in a building. For this reason, the operation of all of them can be synchronized by the central station.
All alarm devices can be assigned to group addresses as well as individual addresses, so that the siren’s functional options are identical to those of the Siren Control Unit – ref. 55000-582 or 55000-182 (DIN rail version).
Mechanical construction
Alarm devices have a base that is fitted to the mounting surface and connected as a ‘first fix’.
Device Addressing
Open area alarm devices respond to their own individual address set with a DIL switch.
They can also respond to a ‘Group Address’ which allows several sirens to be controlled simultaneously. A group address can be any spare address between 112 and 126 and is selected using a 4-segment DIL switch. A device under group address control must have an individual address between 1 and 111, otherwise a fault value of 4 is transmitted. Devices that do not use the group address feature can be addressed at any address (1-126).
Communication
Compatible with XP95, Discovery and CoreProtocol
Backwards compatibility
Alarm devices only operate with control equipment that uses Apollo protocols. The functionalities of open area alarm devices are only available when the device is connected to a central station with the appropriate software.
Main Features
- Fault monitoring self-test
- Choice of tones on the standard device: Apollo, Slow Whoop and DIN
- Two volume settings 92dB(A) and 100dB(A)
- Tone synchronization
- Individual and group addressing
- Integrated insulator
- Red or white options
- Loop-powered
- IP65 rated