Electrical Description
The control panel is loop-powered and operates at 17-28V DC for all variants.
Operation
The address of each panel is set during commissioning by means of a seven-segment DIL switch.
A red alarm LED is provided on the panel. This LED is controlled independently of the panel by the fire control panel.
Once activated, the panel can be reset by inserting the reset key into the front LED, turning it clockwise until it clicks and resets.
The isolated version of the panel incorporates a short-circuit isolator which will guarantee its operation in the event of a short-circuit fault in the loop. The operation of the isolator is indicated by a yellow LED. For more details on the isolator, see data sheet PP2090, available on request.
Mechanical construction
The components of the manual call point are molded in fire-resistant polycarbonate. Data sheet PP2454 shows the dimensions of the mounting hole and the available cable glands, and data sheet PP2454 shows the overall dimensions.
Communication
Protocol – device behavior:
(Dependent on the fire station)
XP95 – XP95
Discovery – Discovery
CoreProtocol – Discovery
Additional information
IP-rated installations
Apollo recommends installing the waterproof panel using the cable entry at the bottom. It is important that cable glands with the correct IP rating are used to ensure that the IP rating of the device is not compromised. All unused cable glands and cable entry sealing plugs must be fully tightened and sealed to ensure that the IP integrity is maintained. The use of PTFE or similar sealant is recommended.
Key features
- Approved according to EN 54-11 (EN 54-17 for the Insulator version)
- Unique ergonomically designed key for resetting and removing the front cover