Discovery Addressable Manual Call Point

Reference: SA5900-908APO
Brand:
In stock

Designed to operate in a loop of intelligent fire detection devices. An alarm is initiated by pressing the reset element. The panel signals the Control and Indication Devices using an interrupt feature within the Apollo Digital Protocol. An alarm status is indicated by rotating the reset element, displaying yellow and black indication bars and a solid red LED. The panel can be reset easily from the front using the key supplied.

Share

Electrical Description
The Smart Button is loop-powered and operates on 17-35V DC.

Operation
The manual call point address is set during commissioning by means of a DIL switch.

The panel has a solid red alarm LED. This LED is controlled independently of the panel by the fire detection panel. The LED flashes yellow if there is a fault and flashes green when the device is polling. Configurable according to Discovery and CoreProtocol.

Once activated, the panel can be reset by inserting the reset key into the front LED and turning it clockwise until it clicks.

The panel incorporates a short-circuit isolator which guarantees its operation in the event of a circuit failure. The operation of the isolator is indicated by a solid yellow LED. For more details on the isolator, see data sheet PP2090, available on request.

This panel helps reduce installation time, as all the initial installation wiring is connected to a removable terminal block that fits neatly into the back of the panel.

Mechanical construction
The components of the manual call point are molded in fire-resistant polycarbonate.

Communication
Compatible with XP95, Discovery and CoreProtocol.

Backward compatibility
The panel operates with Apollo-compatible control panels, using the XP95, Discovery and CoreProtocols digital protocols.

EMC Directive 2014/30 / EU
The key fob complies with the essential requirements of EMC Directive 2014/30 / EU, provided it is used as described.

A copy of the Declaration of Conformity is available on request.

Compliance of the panel with the EMC Directive does not confer compliance with the directive on any device or system connected to it.

Construction Products Regulation 305/2011
The manual call point complies with the essential requirements of Construction Products Regulation 305/2011.

A copy of the Performance Statement is available upon request.

Main Features

  • Reset operating element
  • Easy access, front reset mechanism
  • E-Z connection system for installation
  • Ergonomic reset switch
  • Certified according to EN 54-11 and EN 54-17
  • LED visible at 170°
  • Continuity link for cable insulation testing
  • Suitable for semi-built-in or surface mounting

Sem características de produto para apresentar.

Discovery Installation Guide
Discovery Information product range
Discovery Manual Callpoint Datasheet

Manufacturer information

Manufacturing information includes the address and related information of the product manufacturer

No information to present at the moment.

Responsible EU person

EU-based economic operator who guarantees that the product complies with the required regulations.

No information to present at the moment.

Product safety images

Product safety images contain information about product packaging and can provide key safety information for a specific product.

No information to present at the moment.

Related Products

Waterproof Manual Call Point with Isolator

Find out more about this product. Contact us for more information.

Por favor preencha o formulário abaixo para solicitar mais informações.

Please fill in the form below to request more information.