Electrical Description
The base with integrated siren is loop-powered and does not require an external power supply. It operates at 17-28V DC and is polarity sensitive.
Mechanical construction
The base with integrated siren is molded in polycarbonate and has stainless steel contacts that accept solid or stranded cables up to 2.5mm².
Device addressing
ADDRESSING
The integrated base siren responds to its own individual address set with a DIL switch. It also responds to a group address, set using a 4-segment DIL switch, and to a pulse mode synchronization address that is built into the unit.
GROUP ADDRESSING
It may be desirable, in alarm conditions, to switch the status of more than one integrated base sounder simultaneously. To enable this, the sounders can be controlled as a group and given a group address that is common to all the sounders in the group. When a device recognizes the group address, it processes the routing command bits, but does not return any data to the control panel at that address. If it is necessary to confirm the status of the outputs of devices under group address control, it is necessary to interrogate all the devices in the group at their individual addresses.
Communication
Compatible with XP95, Discovery and CoreProtocol
Backward compatibility
The features of the integrated base siren are only available when the siren is connected to a central station with the appropriate software.
Additional information
For more details, see the Installation Guides (39214-210, 39214-305) and the Data Sheets (PP2209, PP2227, PP2203 and PP2090).
Additional Information 1
For more details, see the Installation Guide – 39214-210 and the Data Sheets (PP2209, PP2203 and PP2090).
Key features
- Two tones
- Two volume ranges 55-75dB (A) and 75-91dB (A)
- Individual and group addressing
- Single acoustic self-test
- Built-in insulator